info@kps.com.vn
+84 903 709 019
The devices receive power, address, and individual control through the Simplex FACU IDNAC SLC, while speakers use a separate NAC audio circuit. They support Class B T-tap wiring for both SLC and audio, reducing cable costs and lengths. Installation is on a standard 4x4 in. electrical box with 2 1/8 in. (54 mm) depth or on a surface-mount/weatherproof (WP) back box. Models are available with standard frequency response (400–4000 Hz) or High Fidelity (200–10,000 Hz), and “-BA” suffix models are assembled in the USA.
Device, cover, back box, and wire guard are designed as separate components, providing flexibility for installation, maintenance, and replacement.
Flame-retardant plastic housing with easily removable cover for convenient inspection or servicing.
Terminal blocks accept 18–12 AWG wiring with loop in/out support to simplify installation and save time.
Integrated LED supervision and magnet test for quick operational checks.
Compliant with ADA and NFPA 72, including the 520 Hz requirement for sleeping areas to enhance occupant safety.
Speaker power taps: ¼W, ½W, 1W, 2W @ 25/70.7 Vrms to accommodate various applications.
Listed and approved by UL 1480, ULC S541, and FM for reliability and code compliance.
Overall dimensions: 8 1/8" x 7 1/8" x 3" (206 x 180 x 76 mm).
Environmental (Non-WP): 0°C to 49°C, RH 10–93%.
Environmental (WP):
UL/ULC: –40°C to 66°C (depending on candela rating)
FM: –40°C to 49°C
RH 95% @ 60°C
Audio:
25 / 70.7 Vrms
¼W: 79 dBA | ½W: 83 dBA | 1W: 86 dBA | 2W: 89 dBA
High Fidelity models ~2–3 dB lower
Strobe Distribution (UL):
On-axis: 327% (vs. 100% requirement)
Off-axis: 45° ~129%, 90° ~47% (exceeds UL standard)
IDNAC SLC:
23–30 VDC regulated
127 addresses / 139 unit loads
Max 10,000 ft (T-tap wiring)
Max 4,000 ft point-to-point (8,000 ft with 4009 Repeater)
Flash rate: 1 Hz
Current Consumption @ 23 V:
49SV / 49HFV:
15 cd: 59 mA
30 cd: 82 mA
75 cd: 145 mA
110 cd: 193 mA
49SVH / 49HFVH:
110 cd: 259 mA
135 cd: 281 mA
185 cd: 325 mA
Weatherproof:
Inside 110 cd: 305 mA
Outside 110 cd: 308 mA
135 cd: 335 mA
185 cd: 398 mA
Table 1 – Standard S/V (APPLC):
49SV-APPLC, 49SV-APPLC-BA
Table 2 – High Fidelity:
49HFV-APPLC, 49HFV-APPLC-BA
Table 3 – High Candela:
49SVH-APPLC, 49SVH-APPLC-BA
Table 4 – HF High Candela:
49HFVH-APPLC, 49HFVH-APPLC-BA
49HFVH-APLCA-BA (amber lens)
Table 5 – Required Covers:
Red / White / Black with multiple legends: ALERT, FIRE, FEU, FUEGO, Simplex logo, or blank.
Table 6 – Weatherproof Models:
49SVH-APPLC-O
49SVH-APPLC-CO (Canada only)
Table 7 – WP Covers:
FIRE, ALERT, FEU, حريق/FIRE, Simplex logo.
Table 8 – Back Box:
49WPBB-SVCR (Red)
49WPBB-SVCW (White)
Table 9 – Wire Guards:
49WGBB-SVCR-O (WP back box, red)
49WG-SVWCR (ceiling guard, red)
4100ES + EPS/EPS+ (S4100-0100)
4009 IDNAC Repeater (S4009-0004)
4100ES Amplifiers 35/50/100W
4100ES Constant Supervision & Signal Cards (S4100-0034)
Simplex Foundation Series 2050FS & 2250FS fire alarm system – smart, flexible, safe fire alarm center for all projects.
View detail
The Simplex 2004FS fire alarm control unit (FACU) delivers flexible initiating circuit monitoring for areas requiring one to four initiating zones.
View detail
Simplex 4007ES addressable fire alarm control panel – powerful, flexible solution for small to medium sized projects, supporting network connectivity and system integration.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Simplex 4017ES addressable fire alarm control panel supports up to 250 IDNet2 points, integrated IDNAC 4A power source, Class A/X digital audio, compatible with TrueAlarm sensors.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Điện thoại cứu hỏa Simplex liên lạc hai chiều giữa trung tâm và lính cứu hỏa, lắp âm/nổi, chống phá hoại, đạt chuẩn UL, FM
View detail
The Simplex 2008FS Fire Alarm Control Unit (FACU) provides flexible initiating circuit supervision and extensive programmable control for areas requiring one to eight initiating zones.
View detail
The Simplex 2004FS fire alarm control unit (FACU) delivers flexible initiating circuit monitoring for areas requiring one to four initiating zones.
View detail
Simplex 4099-5203/5204 Addressable Callpoints – MX Loop fire alarm push button, LED display, easy to maintain, for indoor & outdoor use (IP67).
View detail
2010 © Bản quyền thuộc KPS
Online: 39 | Visitors Counter: 14158427