info@kps.com.vn
+84 903 709 019
Product Code: 2004FS
Product Line: Fire Alarm Controller
Brand: Simplex
Origin: USA
The Simplex 2004FS Fire Alarm Control Unit (FACU) provides flexible initiating circuit monitoring for areas requiring one to four initiating zones.
Convenient display & setup: Status LEDs, DIP switch settings on the main board, USB connection to PC for configuration, event log viewing, and software updates.
Built-in DACT: Supports Contact ID format, silent or audible system walk test mode.
4 standard IDC circuits: Class B, individual zone disable, supports photoelectric smoke detectors, heat detectors, combination detectors, and manual pull stations.
1 standard NAC circuit: Class A/B, 1.5A, supports SmartSync™ horn/strobe control or synchronized strobe.
Standard power supply: 3A @ 24V DC, auto-sensing 120VAC or 240VAC input, battery charger supports up to 12.7Ah.
Other features: 3 auxiliary relays, red cabinet, UL 864 listed, optional city circuit module and remote LED annunciators.
Input voltage: 120VAC, 60Hz or 240VAC, 50Hz (auto-sensing)
Input current:
4A max @ 120VAC
3A max @ 240VAC
Power supply output: 3A max @ 24VDC (in alarm)
Battery charger: Temperature-compensated, supports up to 12.7Ah
Standby current: 136mA (4 fully loaded IDCs, tone-alert silenced, trouble LED on)
1.5A max @ 24VDC (Class A or Class B)
Class B EOL resistor: 10kΩ, 1/2W (Model 4081-9008)
Supervisory current: max 9mA
Alarm current: max 60mA
Each IDC supports up to 20 detectors (smoke or heat) and manual pull stations
Maximum wiring resistance: 50Ω
Class B EOL resistor: 3.3kΩ, 1/2W (Model 4081-9002)
Supports up to 2 annunciators
18 AWG twisted pair, max 4000 ft (1219 m)
Line end resistor or resistor at farthest device required
Recommended overvoltage protector: 2081-9044 for outdoor/indoor wiring transitions
Aux 1 & Aux 2: total 250mA @ 24VDC
Relay 1: Trouble output
Relay 2 & 3: Programmable, 2A @ 30VDC, selectable N.O. or N.C.
IDC, NAC, Aux: 18 AWG – 12 AWG
Annunciator: 22 AWG – 14 AWG
AC input: 14 AWG – 12 AWG
Simplex Foundation Series 2050FS & 2250FS fire alarm system – smart, flexible, safe fire alarm center for all projects.
View detail
Simplex 4007ES addressable fire alarm control panel – powerful, flexible solution for small to medium sized projects, supporting network connectivity and system integration.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Simplex 4017ES addressable fire alarm control panel supports up to 250 IDNet2 points, integrated IDNAC 4A power source, Class A/X digital audio, compatible with TrueAlarm sensors.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Điện thoại cứu hỏa Simplex liên lạc hai chiều giữa trung tâm và lính cứu hỏa, lắp âm/nổi, chống phá hoại, đạt chuẩn UL, FM
View detail
The Simplex 2008FS Fire Alarm Control Unit (FACU) provides flexible initiating circuit supervision and extensive programmable control for areas requiring one to eight initiating zones.
View detail
The Simplex 2004FS fire alarm control unit (FACU) delivers flexible initiating circuit monitoring for areas requiring one to four initiating zones.
View detail
Simplex 4099-5203/5204 Addressable Callpoints – MX Loop fire alarm push button, LED display, easy to maintain, for indoor & outdoor use (IP67).
View detail
Simplex IDNet Addressable Modules add addressing, monitoring & control to common devices, enhancing safety and system integration.
View detail
2010 © Bản quyền thuộc KPS
Online: 41 | Visitors Counter: 14161594
About | Recruitment | News | Contact Us