info@kps.com.vn
+84 903 709 019
The 4090-9120 is a single-address (Six Point Module) of the Simplex fire alarm system, providing:
4 T-Sense supervised inputs: monitor Normally Open (NO) dry contacts, distinguishing four conditions:
Normal: open circuit with EOL resistor
Open Circuit: loss of EOL → Trouble
Short: contact closed directly (e.g., Damper Closed, Fire Alarm)
Current Limited: contact closed through a series resistor (e.g., Damper Open, Supervisory)
2 Relay outputs (Form C, SPDT): control external devices (e.g., fans, dampers, motors, valves).
The module occupies only one IDNet address, but actually provides up to 6 I/O points (displayed as sub-points on the control panel).
Six points combined in one module → saving addresses, wiring, and space.
Typical applications:
Controlling fans/dampers and monitoring multiple feedback conditions.
Monitoring fire pump motor running, low fuel pressure, dual damper feedback.
Compact design:
Fits standard 4-inch (102 mm) electrical box.
Includes communication LED indicator.
Optional faceplates with LED viewing window available.
Relay specifications:
2 A @ 30 VDC (resistive)
0.5 A @ 120 VAC (resistive)
Power source: 24 VDC from UL-listed fire alarm power supply.
Electrical
Communication: IDNet, 1 address
Power supply: 18–32 VDC (nominal 24 VDC)
Current consumption: max 30 mA @ 24 VDC (from UL-listed fire alarm power supply)
Point Allocation
6 points per module:
4 supervised T-Sense inputs
2 relay outputs
Up to 7 reported points including trouble reporting
Inputs
Contact type: Normally Open (NO), dry contact
Wiring distance: up to 500 ft (152 m) per channel (indoor only)
Supervision resistors: requires two per T-Sense input (see accessories: 4081-9003, 4081-9004, 4081-9005)
Wiring connections: screw terminals, 18–14 AWG (0.82–2.08 mm²)
Outputs (Relays)
Contact type: Form C (SPDT)
Not for direct incandescent lamp loads
Power-limited loads:
2 A @ 30 VDC (resistive)
1 A @ 30 VDC (inductive)
Non-power-limited loads:
0.5 A @ 120 VAC (resistive)
0.25 A @ 120 VAC (inductive)
Requires proper fusing and transient suppression (diode for DC, RC network or varistor for AC)
IDNet Wiring Distance
Up to 2,500 ft (762 m) from control panel to farthest device
Up to 10,000 ft (3,048 m) total wiring including T-taps
Compatible with 2081-9044 Overvoltage Protector
Mechanical
Dimensions: 105 × 105 × 35 mm (4-1/8″ H × 4-1/8″ W × 1-3/8″ D)
Material: galvanized steel enclosure
Operating temperature: 0–49 °C (32–120 °F), indoor only
Humidity: 10–90% RH @ 32 °C (90 °F), non-condensing
Installation Instructions: 574-876
4090-9120 – Six Point Module (4 T-Sense Inputs + 2 Relay Outputs)
4090-9801 – Trim plate for semi-flush mount (galvanized steel, LED window, includes screws)
4090-9802 – Trim plate for surface mount
4081-9004 – 6.8 kΩ, 1/2 W – standard EOL resistor for NO contact monitoring
4081-9003 – 4.7 kΩ, 1/2 W – for current-limited monitoring circuits
4081-9005 – 1.8 kΩ, 1/2 W – optional application resistor
Simplex Foundation Series 2050FS & 2250FS fire alarm system – smart, flexible, safe fire alarm center for all projects.
View detail
The Simplex 2004FS fire alarm control unit (FACU) delivers flexible initiating circuit monitoring for areas requiring one to four initiating zones.
View detail
Simplex 4007ES addressable fire alarm control panel – powerful, flexible solution for small to medium sized projects, supporting network connectivity and system integration.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Simplex 4017ES addressable fire alarm control panel supports up to 250 IDNet2 points, integrated IDNAC 4A power source, Class A/X digital audio, compatible with TrueAlarm sensors.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Điện thoại cứu hỏa Simplex liên lạc hai chiều giữa trung tâm và lính cứu hỏa, lắp âm/nổi, chống phá hoại, đạt chuẩn UL, FM
View detail
The Simplex 2008FS Fire Alarm Control Unit (FACU) provides flexible initiating circuit supervision and extensive programmable control for areas requiring one to eight initiating zones.
View detail
The Simplex 2004FS fire alarm control unit (FACU) delivers flexible initiating circuit monitoring for areas requiring one to four initiating zones.
View detail
Simplex 4099-5203/5204 Addressable Callpoints – MX Loop fire alarm push button, LED display, easy to maintain, for indoor & outdoor use (IP67).
View detail
2010 © Bản quyền thuộc KPS
Online: 12 | Visitors Counter: 14558776
About | Recruitment | News | Contact Us