The 4090-9118 Relay IAM with T-Sense is a single-address module of the Simplex fire alarm system, combining:
T-Sense Input (Supervised Input): monitors two different contact states (via series resistor and short circuit), allowing multiple condition distinctions (e.g., damper open/closed, waterflow/tamper).
Relay Output: controls external devices (fan, damper, valve, etc.).
All functions work with just one IDNet address, powered directly from the communication channel, helping save addresses, reduce wiring, and integrate monitoring + control in the same module.
Dual-Point Operation
One T-Sense input to monitor dry contact states via an end-of-line resistor.
One relay output (Form-C, SPDT: one normally closed, one normally open contact) to control external devices.
The T-Sense input can report the following conditions:
Normal: all contacts open with continuity through the EOL resistor.
Open (circuit break): no continuity to EOL resistor → Trouble.
Short: contact closed directly across input circuit.
Current Limited: contact closed with a series resistor → "current limited" state.
The module receives power and data from the IDNet channel of the fire alarm control panel.
No separate power supply required.
The relay defaults to OFF when first powered up or when IDNet communication is lost.
Monitoring open/closed position of valves, doors, or dampers with feedback.
Supervising waterflow, tamper, or other events requiring Trouble / Supervisory / Alarm reporting based on contact states.
| Parameter | Value |
|---|---|
| Module type | Relay IAM with T-Sense (Input + Relay Output) |
| Power/Communication | IDNet channel, single address |
| Operating voltage | 24–40 VDC with IDNet signaling |
| Relay contact ratings | - DC low voltage: 2 A @ 30 VDC (resistive), 1 A @ 30 VDC (inductive) - AC high voltage: 0.5 A @ 120 VAC (resistive), 0.25 A @ 120 VAC (inductive) |
| Relay type | Form-C (SPDT) |
| T-Sense input wiring distance | ≤ 500 ft (152 m) indoor wiring, dry contact NO |
| Supervision / EOL resistors | Two resistors: ~4.7 kΩ and ~1.8 kΩ, ½ W for different supervision states (EOL, current limited) |
| Input states via resistors | • Normal: EOL resistor • Current Limited: series resistor before contact • Short: contact closed directly |
| Dimensions | ~105 × 105 × 35 mm (H × W × D) |
| Operating temperature | 32 °F to 120 °F (0 °C to +49 °C) |
| Relative humidity | 10–90% RH, non-condensing @ ~32 °C |
| Addressing | DIP switch (8-position), 1–250 addresses |
4090-9801: Semi-flush trim plate with LED view hole after cover installation.
4090-9802: Surface-mount trim plate with LED indicator.
4090-9813: Adapter plate for 4-11/16” (119 mm) square electrical box.
End-of-Line Resistor Harnesses: e.g., 733-896 (4.7 kΩ, ½ W), 733-984 (1.8 kΩ, ½ W) for proper supervision states.
Simplex Foundation Series 2050FS & 2250FS fire alarm system – smart, flexible, safe fire alarm center for all projects.
View detail
The Simplex 2004FS fire alarm control unit (FACU) delivers flexible initiating circuit monitoring for areas requiring one to four initiating zones.
View detail
Simplex 4007ES addressable fire alarm control panel – powerful, flexible solution for small to medium sized projects, supporting network connectivity and system integration.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Simplex 4017ES addressable fire alarm control panel supports up to 250 IDNet2 points, integrated IDNAC 4A power source, Class A/X digital audio, compatible with TrueAlarm sensors.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Điện thoại cứu hỏa Simplex liên lạc hai chiều giữa trung tâm và lính cứu hỏa, lắp âm/nổi, chống phá hoại, đạt chuẩn UL, FM
View detail
The Simplex 2008FS Fire Alarm Control Unit (FACU) provides flexible initiating circuit supervision and extensive programmable control for areas requiring one to eight initiating zones.
View detail
The Simplex 2004FS fire alarm control unit (FACU) delivers flexible initiating circuit monitoring for areas requiring one to four initiating zones.
View detail
Simplex 4099-5203/5204 Addressable Callpoints – MX Loop fire alarm push button, LED display, easy to maintain, for indoor & outdoor use (IP67).
View detail
2010 © Bản quyền thuộc KPS
Online: 15 | Visitors Counter: 14562104
About | Recruitment | News | Contact Us