The 4090-9116 Addressable IDNet Communications Isolator is an isolator device used in IDNet communication circuits within addressable fire alarm systems.
Purpose:
When a fault such as a short circuit or earth fault occurs on the signaling line circuit (SLC or IDNet), the device isolates the faulty segment so that the rest of the system continues to operate normally.
It is addressable, allowing it to be monitored and managed by the Fire Alarm Control Panel (FACP).
Circuit Isolation in Case of Short Circuit:
Compatible with Simplex® 4007ES, 4008, 4010ES, 4100ES, 4100U FACPs.
Supports IDNet circuit types: IDNet, IDNet+, IDNet 1+, IDNet 2, IDNet 2+2.
Automatically isolates upon detecting a short circuit; can also be isolated from the panel for diagnostic support.
Each port can be either input or output, independently isolated when a fault occurs.
Supports Class B and Class A Wiring:
In Class A configuration, maintains communication with devices outside the faulted zone.
When installed at the beginning and end of a Class A loop, protects the entire loop from short circuits.
Earth Fault Diagnostics:
The control panel can locate earth faults without requiring extensive wire disconnection.
Allows isolation by floor/segment to narrow down the fault area.
Status Monitoring:
Reports isolation status back to the panel.
The panel can identify devices that are not communicating, pinpointing the fault zone.
Design & Installation:
Fits standard 4” (102 mm) square electrical box; adapter available for 4-11/16” (119 mm) box.
LED indicator shows communication activity; optional transparent cover for easy viewing.
Dimensions: 105 × 105 × 35 mm.
Black plastic housing mounted on metal base.
Electrical
Communication: IDNet (1 address per device).
Compatibility: Simplex 4007ES, 4008, 4010ES, 4100ES, 4100U FACPs (supports IDNet, IDNet+, IDNet 1+, IDNet 2, IDNet 2+2).
(Not compatible with 4100-3103 Panel Mounted Quad Isolator).
Power: Consumes 1 unit load, powered directly from IDNet SLC.
Wiring: Screw terminals for input and output, supports 18–14 AWG (0.82–2.08 mm²) wire.
Wiring Distance
From panel to isolator: up to 2,500 ft (762 m).
Total loop length (including T-Taps): up to 10,000 ft (3048 m).
Maximum resistance between panel and isolator, or between isolators: 10 Ω.
With 18 AWG (0.82 mm²) wire ≈ 780 ft (238 m).
Compatible with Simplex 2081-9044 Overvoltage Protectors.
Mechanical
Dimensions: 105 mm (H) × 105 mm (W) × 35 mm (D) ≈ 4 ⅛” × 4 ⅛” × 1 ⅜”.
Materials: Black thermoplastic housing on metal base.
Environmental
Operating Temperature: 0° to 49°C (32°–120°F), indoor use only.
Humidity: 10% – 90% RH at 32°C (non-condensing).
4090-9116 → Addressable IDNet Communications Isolator (main device).
4090-9813 → Adapter plate for 4 11⁄16” (119 mm) square box.
4090-9801 → Semi-flush trim plate with LED viewing window, includes mounting screws.
4090-9802 → Surface-mounted box trim plate, galvanized steel, with LED viewing window.
Simplex Foundation Series 2050FS & 2250FS fire alarm system – smart, flexible, safe fire alarm center for all projects.
View detail
The Simplex 2004FS fire alarm control unit (FACU) delivers flexible initiating circuit monitoring for areas requiring one to four initiating zones.
View detail
Simplex 4007ES addressable fire alarm control panel – powerful, flexible solution for small to medium sized projects, supporting network connectivity and system integration.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Simplex 4017ES addressable fire alarm control panel supports up to 250 IDNet2 points, integrated IDNAC 4A power source, Class A/X digital audio, compatible with TrueAlarm sensors.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Điện thoại cứu hỏa Simplex liên lạc hai chiều giữa trung tâm và lính cứu hỏa, lắp âm/nổi, chống phá hoại, đạt chuẩn UL, FM
View detail
The Simplex 2008FS Fire Alarm Control Unit (FACU) provides flexible initiating circuit supervision and extensive programmable control for areas requiring one to eight initiating zones.
View detail
The Simplex 2004FS fire alarm control unit (FACU) delivers flexible initiating circuit monitoring for areas requiring one to four initiating zones.
View detail
Simplex 4099-5203/5204 Addressable Callpoints – MX Loop fire alarm push button, LED display, easy to maintain, for indoor & outdoor use (IP67).
View detail
2010 © Bản quyền thuộc KPS
Online: 87 | Visitors Counter: 14553552
About | Recruitment | News | Contact Us