info@kps.com.vn
+84 903 709 019
The Zone Adapter Module (ZAM), models 4090-9101 and 4090-9106 from Simplex, enables the integration of conventional detection zones into an addressable fire alarm system (IDNet or MAPNET II).
4090-9101: Class B type zone interface, supports 2-wire or 4-wire initiating devices, with reset capability for 4-wire detectors.
4090-9106: Class A type zone interface (loop with two-way wiring), supports 2-wire devices only.
For IDNet systems: Simplex fire alarm panels 4007ES, 4008, 4010, 4010ES, 4100ES, 4100U.
For MAPNET II systems: via CDT Transponders on panels 4100/4100U, 4120, 4020, 2120.
Compatible with IDNet or MAPNET II communications.
Provides one unique address per IDC zone.
Integrated status LED (optional cover plates allow LED visibility after installation).
Screw terminal connections, supports 18–14 AWG wiring.
Sealed design reduces dust accumulation; mounts in standard 4” (102 mm) square box.
UL listed to standard UL 864.
Approved for use with Simplex control panels:
IDNet: 4007ES, 4008, 4010, 4010ES, 4100ES, 4100U
MAPNET II: 4100/4100U, 4120, 4020, 2120 CDT
Communication: IDNet or MAPNET II, occupies 1 address per module
Input Voltage (ZAM): 18.9 – 32 VDC (24 VDC nominal)
Current Consumption @ 24 VDC:
Supervisory: ≤ 16 mA
Alarm: ≤ 72 mA (depending on number of devices)
End-of-Line Resistor (4090-9101 only): 3.3 kΩ, 1 W
Wiring Distance:
Up to 762 m (2500 ft) from FACP
Up to 3048 m (10,000 ft) total, including T-Taps
Dimensions: 105 × 105 × 35 mm (4 ⅛” × 4 ⅛” × 1 ⅜”)
Housing Material: Black thermoplastic
Mounting Plate: Galvanized steel
Operating Environment:
Temperature: 0° – 49 °C (32° – 120 °F), indoor use only
Humidity: ≤ 93% RH at 38 °C, non-condensing
Certifications: UL, ULC, CSFM, FM, NYC MEA
2-wire photoelectric smoke detectors: 2098-9209 (up to 20 devices per IDC)
Electronic heat detectors: 4098-9401, 9402, 9403, 9404, 9612, 9613… (up to 20 devices per IDC)
Ionization smoke detectors: 4098-9603 (up to 20 devices per IDC)
Duct detectors: 4098-9685 (up to 20 devices per IDC)
Some special models (e.g., 4098-9683, 4098-9684) allow 1 device per IDC only.
4090-9813: Adapter plate for 119 mm (4-11/16”) box
4090-9801: Flush-mount plate, galvanized steel, with LED window
4090-9802: Surface-mount plate
4081-9002: 3.3 kΩ, 1 W End-of-Line Resistor (for 4090-9101 Class B zones)
Simplex Foundation Series 2050FS & 2250FS fire alarm system – smart, flexible, safe fire alarm center for all projects.
View detail
The Simplex 2004FS fire alarm control unit (FACU) delivers flexible initiating circuit monitoring for areas requiring one to four initiating zones.
View detail
Simplex 4007ES addressable fire alarm control panel – powerful, flexible solution for small to medium sized projects, supporting network connectivity and system integration.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Simplex 4017ES addressable fire alarm control panel supports up to 250 IDNet2 points, integrated IDNAC 4A power source, Class A/X digital audio, compatible with TrueAlarm sensors.
View detail
Simplex 4010ES – addressable fire alarm panel, supports 250-1,000 points, IP networking, touch screen, compatible with TrueAlarm & TrueAlert ES.
View detail
Điện thoại cứu hỏa Simplex liên lạc hai chiều giữa trung tâm và lính cứu hỏa, lắp âm/nổi, chống phá hoại, đạt chuẩn UL, FM
View detail
The Simplex 2008FS Fire Alarm Control Unit (FACU) provides flexible initiating circuit supervision and extensive programmable control for areas requiring one to eight initiating zones.
View detail
The Simplex 2004FS fire alarm control unit (FACU) delivers flexible initiating circuit monitoring for areas requiring one to four initiating zones.
View detail
Simplex 4099-5203/5204 Addressable Callpoints – MX Loop fire alarm push button, LED display, easy to maintain, for indoor & outdoor use (IP67).