info@kps.com.vn
+84 903 709 019
Module generates 1 input
Control valves, flow switches, pumps, fans, water levels,...
Electric coding, Loop Powered,monitor N/O or N/C dry contact input

SPECIFICATIONS
| Operating Voltage | Loop 24V(16V~28V) |
| Standby Current Active current Programming Method |
0.48mA 0.62mA Electronically addressed |
| Code Range | One address is within 1~ 242. |
|
Cable check |
NO Contact: Fault for open circuit, action when closed NC Contact: Fault for short circuit, action when open |
|
Indicator |
Red Flashes when polling Illuminates in action Double flashes for low power 2.5Hz 50% duty cycle for cable fault |
| Ingress Protection Rating | IP30 |
| Operating Temperature | -10°C ~ 55ºC |
| Relative Humidity | ≤93%, non condensing |
| Material of Enclosure | ABS, white |
| Dimension (L×W×H) |
86mm×86mm×41mm (with base) |
| Weight | About 93g |
SYSTEM