Control module
or N/C dry contact programmable, 1 line passive N/O output( DC30V/2A)
TECHNICAL NUMBERS
| Operating Voltage | Loop: 24V (16V~28V) |
| Standby Current | Loop≤0.46mA |
| Action Current | Loop≤0.72mA |
| Output Capacity | Output contact capacity 30VDC/2A |
| Input cable check | 4k7 OHM EOLR. Fault on open-circuit, or short-circuit for NC input. |
| Output cable check | Fault on open on NO-GND port -circuit and short-circuit |
| Programming Method | Electronically addressed |
| Code Range | One address within 1~242. |
| Input Indicator | Red. Flashes when polling. Illuminates in action. Double flashes for low power. 2.5Hz 50% duty cycle for cable fault. |
| Output indicator | Red. Lit when output activated. 2.5Hz 50% duty cycle for cable fault. |
| Ingress Protection Rating |
IP30 |
| Operating Temperature |
-10°C ~+55°C |
| Relative Humidity | ≤93%, non condensing |
| Material of Enclosure | ABS white |
| Dimension (L×W×H) | 86mm×86mm×41mm (with base) |
| Weight | About 96.6g (with base) |