The DI-M9301 Single Digital Input & Output Module provides a dry contact output (Normally Open and/or Normally Closed) controlled by the Fire Alarm Control Panel (FACP).
It can also receive switching signals (dry contacts) from field devices and transmit them to the FACP.
The input and output can be programmed to monitor and control the same device or different devices.
Class B input wiring with end-of-line supervision using a 4.7kΩ resistor
Input can be programmed to monitor Normally Open (NO) or Normally Closed (NC) dry contacts
Input can be programmed as “self-feedback”, meaning the input supervision is disabled and the module directly sends a status signal to the FACP when the dry contact output changes state
Address can be set on-site using a programmer
Input uses AD sampling technology for accurate detection
Compatible with GST-M200 and GST-IFP4M fire alarm control panels
Easy installation
Standards: UL 864, NFPA 70 & NFPA 72
Operating Voltage: 24VDC loop power (16VDC – 28VDC), power-limited
Standby Current: ≤ 0.28 mA
Operating Current: ≤ 0.7 mA
Output Rating: 2A @ 30VDC, 0.35 PF, Normally Open / Normally Closed
Operating Environment:
Temperature: 0°C to +49°C
Relative Humidity: ≤ 93%, non-condensing
Dimensions: 78 mm × 45.3 mm × 28.5 mm