Addressable sounder base, compatible with addressable detectors JTF- GOM-GST601T,JTY-GD-G3T,JTW-ZCD-G3N, loop powered
NUMBERS TECHNICAL
| Operating Voltage | Loop 24V (16V~28V) |
| Standby Current | ≤1mA |
| Alarm Current | ≤5mA |
| Sound Level | ≥85dB (1m ahead horizontally (A weighted)) |
| Mode | Setting Mode I, Mode II, Mode III, Mode IV through different addresses. |
| Type of Alarm Signal | Pre-alarm: Intermittent (0.5s on 1s off) Fire Alarm: Continuous (0.4s on, 0.3s off) |
| Programming | Electronically addressed |
| Code Range | 1~242 |
| Ingress Protection Rating |
IP31 |
| Operating Temperature |
-10℃~+50℃ |
| Relative Humidity | ≤95%, non condensing |
| Material and Color of Enclosure |
ABS, white (RAL 9016) |
| Dimension | Diameter: 120mm Height: 38.8mm(without cover) |
| Weight | About 150g |