Conventional Ultra-Violet Flame Detector
Conventional Ultra-Violet Flame Detector

TECHNICAL NUMBERS
- Rated working voltage: DC24V Working voltage range: DC16V~DC28V
- Monitoring current: ≤2.5mA Alarm current: ≤15mA
- Output capacity: normally open passive output, contact capacity 1A, DC24V
- Output control mode: self-locking after alarm
- Alarm reset: instantaneous power failure (5sMAX, DC2.5VMAX)
- Power-on time ≤5s
- Indicator light: alarm confirmation light, red, flashing periodically during monitoring, and always on when alarming
- Spectral response range: 185nm~260nm
- Detection distance: The detector has three sensitivity levels, and different sensitivity levels correspond to different detection distances. For the flame produced by burning 2000g of industrial ethanol in a container with a bottom area of 33cm×33cm and a height of 5cm: first level, 25m; second level, 17m; third level, 12m
- Wire system: two-wire system without polarity
- Use environment: temperature: -20℃~+55℃ relative humidity: relative humidity ≤95%, no condensation
- Dimensions: diameter: 103mm, height: 53.5mm (with base) diameter: 100mm, height: 41mm (without base)
- Shell protection grade: IP21
- Shell material and color: ABS, ivory white
- Weight: 110g
- Installation hole distance: 45mm~75mm