Description of UPS Legrand Keor DK 311340
Keor DK 311340 is a 1-phase UPS using On-line Double Conversion VFI technology, 2U size (19” rack) / converted to tower, rated capacity 1 kVA ~ 1 kW (PF = 1).
This UPS is a basic, compact, easy-to-install version, managed by touch screen and standard communication ports. With a design for small depth racks, integrated internal battery, suitable for small servers, important network equipment, camera systems / security equipment, small data rooms and office applications that require clean power and short backup time.
Outstanding features:
- Real capacity 1 kW (PF = 1).
- On-line Double Conversion technology (VFI-SS-11) - completely separates the load from the grid, providing the highest protection for sensitive loads.
- Convertible design 2U (19” rack) / tower - space saving rack space saving, suitable for 600 mm depth cabinets.
- Touch-screen + LED indicator, with gravity sensor to display the correct direction.
- Internal battery - this model comes with an internal battery; reference backup time ~9 minutes.
- High operating efficiency: AC/AC ≈ ~92%; when ECO Mode is on, it can reach ~98% (saving mode).
- Wide input voltage range: stable operation under fluctuating grid power conditions (about 176 V - 280 V at full load).
- Protection & operating features: Cold-start, backfeed protection, EPO (Emergency Power Off), integrated ROO/relay contact (dry contacts).
- Communication & management: USB, RS-232, ROO; SNMP/BMS card connection possible (configuration option).
- Lithium battery ready and supports external charger/upgrade charger (8A optional) to increase runtime if required.
- Standards & safety: EN 62040-1/2/3 compliant; IP20 protection rating; 0–40°C operation.
Specifications
Power & input / output
- Rated power: 1000 VA / 1000 W (PF = 1).
- Technology: On-line double conversion (VFI-SS-11).
- Input voltage: 230 V.
- Input voltage range (full-load): 176 V – 280 V.
- Input frequency: 50/60 Hz ±5% (autosensing).
- Input Power Factor: > 0.99.
- Input current THD: < 5%.
- Output voltage: 230 V ± 1% (in On-line mode).
- Output frequency: 50/60 Hz (configurable via LCD) ± 0.1%.
- THD output voltage: < 3% with linear load.
- Peak (inrush) factor: 3:1.
- Output power factor: 1.0 (kVA = kW).
Battery & backup / charging time
- Battery type: VRLA (built-in standard); lithium-ready if configuration changes.
- Internal battery.
- Internal backup time: ~9 min.
- Standard charging current: 2 A.
- Support for backup time extension with separate battery cabinet.
Dimensions & environment
- Reference dimensions (W x H x D): 440 × 88 (2U) × 454 mm (approx.).
- Reference net weight: ~15 kg.
- Operating temperature: 0 – 40 °C.
- Operating humidity: < 95% non-condensing.
- Noise level at 1 m: < 50 dBA (1 kVA is usually quiet).
- Protection class: IP20.
- Chassis coating: with anti-corrosion coating.
Management & communication
- Display: Touch screen (approx. 3.5” – 4.3” on some variants; 2U models usually equipped with 3.5” or 4.3”).
- LED status bar shows status at a glance.
- Ports: ROO, USB, RS-232; SNMP connector.
- Dry contacts (relay) embedded; EPO (Emergency Power Off) available.
- Backfeed protection: Yes.
- Cold start: Yes.
- Remote control available.
Expandability & deployment requirements
- Parallel operation: Not applicable for 1 kVA models.
- Bypass: Internal automatic bypass included; External maintenance bypass is an optional accessory.
- Genset compatible: Yes.
- Available accessories: rack support kit, external manual bypass, additional charger, dry contact card, parallel kit (for supported models), distribution box.
Standards & certifications
- Compliance: EN 62040-1, EN 62040-2, EN 62040-3.
- Industrial safety/EMC certification.