GST-LD-8360H input module is used to receive the normally open or normally closed switching signal input from the fire linkage equipment, and transmit the linkage information back to the fire alarm controller (linkage type). It is mainly used for mating various active equipment in the field, such as water flow indicators, pressure switches, position switches, signal valves and external linkage devices that can send back switching signals. After these devices act, the output action signal can be sent to the fire alarm controller by the module through the signal two bus, generate an alarm, and can link other related equipment actions through the fire alarm controller.
The GST-LD-8360H input module is factory set to occupy two coding points, and both inputs are normally open inspection lines.
Indicator status description: input 1 indicator (for the signal at the input 1 end), red, the normal state is flashing, the bus voltage is low and the fault is flashing twice in a row, the input fault is flashing at 2.5Hz and 50% duty cycle, and it is always on when there is feedback; Input 2 indicator (for input 2-terminal signal), red, the normal state is off, the input fault flashes at 2.5Hz, 50% duty cycle, and is always on when there is feedback.

|
Operating Voltage |
Loop: 24V (16V~28V) |
|
Standby Current |
Loop≤0.36mA |
|
Action Current |
Loop≤0.58mA |
|
Cable check |
4k7 OHM EOLR. Fault on open |
|
Programming Method |
Electronically addressed |
|
Code Range |
1 address within 1~242, or 2 |
|
Input Indicator |
Red. |
|
Ingress Protection |
IP30 |
|
Operating |
-10°C ~+55°C |
|
Relative Humidity |
≤93%, non condensing |
|
Material of Enclosure |
ABS white |
|
Dimension (L×W×H) |
86mm×86mm×41mm (with base) |
|
Weight |
About 95g (with base) |