info@kps.com.vn
+ 84 903 709 019
|
FAP-O 520 (-P) |
FAP-OC 520 (-P) |
|
|
Electrical |
|
|
|
Operating voltage |
15 V DC to 33 V DC |
15 V DC to 33 V DC |
|
Current consumption |
< 3.25 mA |
< 3.25 mA |
|
Alarm output |
Per data word by two-wire signal line |
Per data word by two-wire signal line |
|
Indicator output |
Open collector connects 0 V over 1.5 kΩ through, max. 15 mA |
Open collector connects 0 V over 1.5 kΩ through, max. 15 mA |
|
Mechanics |
|
|
|
Dimensions |
|
|
|
- Detector |
Ø 113 x 55 mm |
Ø 113 x 55 mm |
|
- Detector with Tim Ring |
Ø 150 x 55 mm |
Ø 150 x 55 mm |
|
- Detector with Trim Ring, Base and Ceiling Mount Back Box |
Ø 150 x 110 mm |
Ø 150 x 110 mm |
|
Housing material |
Polycarbonate |
Polycarbonate |
|
Color |
- Detector housing: Signal white, RAL 9003 |
- Detector housing: Signal white, RAL 9003 |
|
|
- Detector front plate FAP‑O 520/ FAP‑OC 520: Signal white matt |
- Detector front plate FAP‑O 520/ FAP‑OC 520: Transparent/silver-gray |
|
|
- Detector front plate FAP‑O 520‑P/ FAP‑OC 520‑P: Transparent/silver-gray |
- Detector front plate FAP‑O 520‑P/ FAP‑OC 520‑P: Transparent/silver-gray |
|
Weight |
Without / with packaging |
Without / with packaging |
|
- FAP-OC 520(-P) |
180 g / 370 g |
180 g / 370 g |
|
- FAP-O 520(-P) |
170 g / 360 g |
170 g / 360 g |
|
- Trim Ring |
- |
- |
|
Environmental conditions |
|
|
|
Permissible operating temperature |
-20 °C to +65 °C |
-10 °C to +50 °C |
|
Permissible relative humidity |
95% (non-condensing) |
95% (non-condensing) |
|
Permissible air speed |
20 m/s |
20 m/s |
|
Protection class as per EN 60529 |
IP 53 |
IP 33 |
|
Planning |
|
|
|
Monitoring area |
Max. 120 m2 (Heed local guidelines!) |
Max. 120 m2 (Heed local guidelines!) |
|
Maximum installation height |
16 m (Heed local guidelines!) |
16 m (Heed local guidelines!) |
|
Minimum installation height |
Out of arm's reach |
Out of arm's reach |
|
Minimum installation height recommended by BOSCH |
2.70 m |
2.70 m |
|
Minimum distance to lamps |
0.5 m |
0.5 m |
|
For flush ceiling mounting with FAA-500-BB |
- Thickness of the false ceiling: Max. 32 mm |
- Thickness of the false ceiling: Max. 32 mm |
|
|
- Required bored hole Ø 130 mm (-1 mm to +5 mm) |
- Required bored hole Ø 130 mm (-1 mm to +5 mm) |
|
|
- Installation depth: 110 mm |
- Installation depth: 110 mm |
|
|
Note: Above the false ceiling, a free height of at least 110 mm is required. |
Note: Above the false ceiling, a free height of at least 110 mm is required. |
|
Further characteristics |
|
|
|
Detection principle |
Scattered light measurement |
Combination of scattered light measurement and combustion gas measurement |
|
Response sensitivity |
< 0.18 dB/m (EN 54-7) |
Optical section: < 0.36 dB/m (EN 54‑7) Gas sensor section: in ppm range |
|
Individual display |
Two-color LED, red (alarm), green (test mode) |
Two-color LED, red (alarm), green (test mode) |
2010 © Bản quyền thuộc KPS
Online: 25 | Visitors Counter: 13520627