KPS System Corp | Công ty cổ phần Hệ Thống An Ninh Khai Phát

Syncro

Syncro
  • 2 or 4 loop versions as standard (for 6-8
  • loop versions see DS57)
  • Larger enclosure available (fits 24A/H SLAs)
  • Loopless panel option (repeater)
  • 0, 16, 48, or 96 zone indicators
  • Option for Enable Control keyswitch
  • Fully supports Apollo, Argus Vega & Hochiki protocols
  • Network up to 64 panels/repeaters
  • 4 programmable sounder circuits as standard
  • 5.25 amp power supply to EN54 part 4
  • Large graphic display
  • In built help and alarm information screens
  • Certified to EN54-2/ EN54-4
  • Real time clock
  • Supports Apollo, Argus Vega and Hochiki loop
  • powered sounders and beacons
  • Sensitivity adjustment and Drift Compensation
  • Stylish enclosure design
  • Soft-touch tactile buttons
  • 2 programmable function buttons
  • 3 programmable front panel mounted LED’s
  • Improved Front loading Printer (optional)
  • Up to 512 programmable inputs/outputs per panel
  • via 2 wire RS485 serial link (optional)
  • Simple Windows® graphical configuration utility

 

 

Mô tả
Construction 1.2mm mild sheet steel
IP Rating IP30
Finish Epoxy powder coated
Colour - lid & box BS 00 A 05 grey - fne texture
Colour - controls plate & labels RAL 7047 light grey - satin
Weight 10kg (standard panel)
Display 8 lines of 40 characters graphic LCD
Detection circuits (Loops) 2 or 4 (400mA each)
Zone LED’s 0, 16, 48, or 96 (up to 500 software zones)
4 sounder circuits Each fused at 1 Amp (total load 2 Amp)
Fire contact Volt free 1 Amp 30V DC
Alarm contact Volt free 1 Amp 30V DC
Fault contact Volt free 1 Amp 30V DC
Programmable relay 1 Volt free 1 Amp 30V DC
Programmable relay 2 Volt free 1 Amp 30V DC
Fire routing output Monitored-voltage reversing, fused at 500mA
Fault routing output Monitored-voltage reversing, fused at 500mA
Extinguisher output Monitored-voltage reversing, fused at 1A
Fault input Volt free contact input signals fault
Reset input Volt free contact input resets panel
Intermittent input Volt free contact input pulses sounder outputs
Continuous input Volt free contact input for continuous sounders
Silence input Volt free contact input silences sounders
Programmable input 1 Volt free contact for any action required
Programmable input 2 Volt free contact for any action required
Programmable input 3 Volt free contact for any action required
Auxiliary 24V DC output Fused at 500mA
System fuse 5 Amp self-resetting polyfuse
Mains fuse 20mm 3 Amp
Operating Temperature -5 to +50 deg. C
Operating humidity To 95% (non-condensing)
Mains voltage supply 110 or 230V AC 50 or 60 Hz. (specify when ordering, default is 230V)
Battery (24 hour standby) 12Ah 12V (2 per panel) (non-networked)
Day/night modes 2 with variable device sensitivity
Input delays Individual for each device selectable up to 2 minutes
Output delays Individual 2-stage to 10 minutes per stage
2 programmable function buttons Programmable to carry out any cause & effect, disablement or test action
3 programmable indicators Red/yellow/green to indicate any action
Network (option) Up to 64 panels on 2 wires (K555 Network Card required)
Download
Tên File Download
Datasheet › Việt Nam › English

Tin tức công ty

Tin công nghệ

Kinh nghiệm hay

Dịch Vụ

Giải pháp

Dự án

Tuyển dụng

Sản phẩm liên quan

Taktis Vision

Taktis Vision

Taktis Vision Analogue Addressable Annunciators

Taktis Fire

Taktis Fire

Taktis Fire Analogue Addressable 2-16 Loop Control Panels

1 2
Công ty cổ phần Hệ Thống An Ninh Khai Phát (gọi tắt là Công ty KPS). GPDKKD: 0310471658 do sở KH & ĐT TP.HCM cấp ngày 24/11/2010. Đại diện pháp luật: Đinh Tấn Đạt.

2010 © Bản quyền thuộc KPS

Đang Online: 11 | Tổng Truy Cập: 9846682

Giới Thiệu | Tuyển dụng | Tin tức | Liên Hệ

zalo
messenger