KPS System Corp | Công ty cổ phần Hệ Thống An Ninh Khai Phát

Sigma CP Ancillaries

Sigma CP Ancillaries
  • The Sigma Ancillary Board is compatible with all Sigma CP and CP-R panels which have operating software version V2.0 or above.
  • The board provides common fire, common fault, coincidence and zonal fire, volt free contacts allowing control of sub-systems, graphical mimics and plant, remotely from the main panel over a two wire data bus.
  • Mains powered Ancillary boards require only a two core data cable from the main control panel. 24V DC versions require an additional two cores for power either from the main panel or from another 24V DC source.
  • A mixture of Ancillary boards, Sounder boards or Repeaters up to a maximum of 7 of each type can be connected to a control panel and each is allocated an address from 1 to 7 using a binary coded DIL switch. The total length of the data cable from the main panel to the last repeater must not exceed 1200 metres.

Sounder Controller

  • Conventional Sounder controllers enable additional, distributed power and control for sounder circuits in situations where there are insufficient circuits at the fire alarm control panel or where additional power is required to power heavily loaded sounder circuits.
  • The Sounder Controller Unit connects to conventional sounder circuits and any faults on its outputs are transmitted to the fire control panel via the incoming, triggering sounder circuit thus maintaining full fault monitoring.
  • All units contain a mains powered battery charger/power supply. There is space for up to 7 Ah batteries.
  • Indicators are provided for power healthy, power fault and sounder fault conditions and power fault conditions are signalled to the fire alarm control panel as a sounder fault.

 

 

Thông số kĩ thuật 
Construction 1.2mm mild sheet steel
IP Rating IP30
Finish Epoxy powder coated
Colour - lid & box BS 00 A 05 grey - fine texture
Colour - Controls plate & labels RAL 7047 light grey - satin
Weight 6kg
Supply voltage (K models) 230V AC (+10%/-15%)
Supply voltage (E models) 20-30V DC
Mains supply fuse 1.6A 250V
Power supply DC rating 24V 1 Amps
Maximum battery size 7Ah 12V (2 per panel)
Fault contact rating 30V DC 1 Amp
Fire contact rating 30V DC 1 Amp
Cable capacity 2.5mm² per terminal
Operating temperature -5°C to +40°C
Operating humidity <95% (non condensing)
Download
Tên File Download
Datasheet › Việt Nam › English

Tin tức công ty

Tin công nghệ

Kinh nghiệm hay

Dịch Vụ

Giải pháp

Dự án

Tuyển dụng

Sản phẩm liên quan

LCMU

LCMU

LCMU Line Continuity Monitoring Circuit

Series 3000

Series 3000

Series 3000 Conventional Fire Alarm Control Panels

Sigma Matrix

Sigma Matrix

Sigma Matrix Conventional Fire Alarm Mimic System

Sigma CP-R

Sigma CP-R

Sigma CP-R Conventional Fire Control Panel Repeaters

Sigma CP-A

Sigma CP-A

Sigma CP-A AlarmSense Compatible 2 Wire Conventional Fire Control Panels

Sigma CP

Sigma CP

Sigma CP Conventional Fire Control Panels

Công ty cổ phần Hệ Thống An Ninh Khai Phát (gọi tắt là Công ty KPS). GPDKKD: 0310471658 do sở KH & ĐT TP.HCM cấp ngày 24/11/2010. Đại diện pháp luật: Đinh Tấn Đạt.

2010-2019 © Bản quyền thuộc KPS

Đang Online: 6 | Tổng Truy Cập: 8912551

Giới Thiệu | Tuyển dụng | Tin tức | Liên Hệ